ACT20X-HDI-SDO-RNO-S Преобразователь сигналов (8965340000)
Цена не окончательная, действует гибкая система скидок. |
Описание
Характеристики
Общие данные
- Average Probability of Failure on Demand (PFDavg) 2.04 x 10-4 (Tproof = 1 year), 4.08 x 10-4 (Tproof = 2 years), 1.02 x 10-4 (Tproof = 5 years)
- Demand mode High
- Demand rate 1 000 s
- Demand response time < 10 ms (relay output)
- Description of the "safe state" de-energized (relay output)
- Diagnostic test interval 10 s
- Mean Time To Repair (MTTR) 8 h
- MTBF 207 Years
- NAMUR-питание 8 V DC / 8 mA
- Relay lifetime 100000 times
- Safe Failure Fraction (SFF) 90 %
- SIL PAPER SIL certificate
- SIL согласно IEC 61508 2
- Total failure rate for dangerous detected failures (λDD) 130 FIT
- Total failure rate for dangerous undetected failures (λDU) 46 FIT
- Total failure rate for safe detected failures (λSD) 0 FIT
- Total failure rate for safe undetected failures (λSU) 289 FIT
- Tproof 4 Years
- Брошюра / каталог CAT 4.1 ELECTR 16/17 EN
- Вероятность отказа в час PFH 4.66 x 10-8 h-1
- Вид защиты IP20
- Вид соединения Винтовое соединение, Съемный клеммный блок
- Влажность 0...95 % (без появления конденсата)
- Входное сопротивление 1 кОм
- Высокий пороговый уровень > 2.1 мA
- Высота 117,2 мм
- Выходной сигнал при обрыве провода < 0.1 мA, > 6.5 мA
- Глубина 113,6 мм
- Глубина (дюймов) 4,472 inch
- Датчик NAMUR-Чувствительность в соответствии с EN60947, переключение с или без RS, RP
- Диапазон зажима, макс. 2,5 mm²
- Диапазон зажима, мин. 0,5 mm²
- Диапазон размеров зажимаемых проводников, измерительное соединение, 2,5 mm²
- Длительность импульса < 0,1 мс
- Исполнение EX-преобразователь сигналов, Вход Ex: датчик/коммутатор NAMUR, Безоп. выход: реле, контакт НР, 1-канальн.
- Категория безопасности SIL 2
- Коммутационная способность AC 500 ВА/60 Вт (безопасная область), 16 ВА/60 Вт (зона 2)
- Конфигурация с программным обеспечением FDT/DTM
- Масса нетто 177 g
- Момент затяжки, макс. 0,6 Nm
- Момент затяжки, мин. 0,4 Nm
- Мощность P0 32 mW
- Напряжение U0 10.6 В DC
- Напряжение питания 19,2…31,2 В DC
- Напряжение развязки 2 кВ, вход / выход / питание
- Непрерывный ток ≤ 0,5 A AC / 0,3 A DC (безопасная зона), ≤ 0,5 A AC / 1 A DC (зона 2)
- Низкий уровень триггера < 1.2 мA
- Номинальное рабочее напряжение ≤ 125 В AC / 110 В DC (взрывозащенная область),≤ 32 В AC / 32 В DC (Зона 2)
- Норма упаковки (VPE) 1 Шт.
- Нормы по ЭМС DIN EN 61326, NE 21
- Обозначение II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Одобрение / сертификат / документ о соответствии SIL certificate Certification DNV GL Declaration of Conformity
- Отказоустойчивость оборудования (HFT) 0
- Питание датчика 8 V DC / 8 mA
- Пользовательская документация Instruction sheet Manual MAN SAFETY ACT20X-(2)HDI-(2)SDO-RNx
- Поперечное сечение подключаемого провода AWG, макс. AWG 14
- Поперечное сечение подключаемого провода AWG, мин. AWG 30
- Потребляемая мощность ≤ 1,3 Вт
- Программное обеспечение WI-Manager, DTM-Library for online installation V.1.2.0
- Рабочая температура -20 °C...60 °C
- Рабочая температура, макс. 60 °C
- Рабочая температура, мин. -20 °C
- Расчетное напряжение 300 В
- Сведения об изделии Для этого устройства компания Weidmüller предоставляет увеличенный гарантийный период (36 месяцев).
- Сертификат ATEX 09ATEX0168X.pdf
- Сертификат IECEx IECEx certification
- Сертификат UL E337701.pdf
- Сертификат № (ATEX) KEMA09ATEX0168X
- Сертификат № (IECEX) IECEXKEM09.0072X
- Сопротивление RP = 750 Ω / RS = 15kΩ
- Текст описания, длинный Усилитель-разъединитель для датчиков Namur для применения во взрывоопасных зонах Ex, ,1-канальный усилитель-разъединитель с монтажной шириной 22,5 мм с внешним электропитанием,,для развязки и передачи сигналов датчика Namur из зоны Ex 0, 1, 2 в безопасную зону. ,На выходе предоставляется беспотенциальный релейный контакт с функцией нормально разомкнутого контакта и контакт аварийной сигнализации для ,сообщений о состоянии/ ошибке.,Предусмотрена возможность конфигурирования модуля при помощи стандартного программного обеспечения FDT/DTM.Корпус для установки в ряд на монтажную рейку TS35,Размеры: Д/Ш/В 119,2/ 22,5/ 113,6,Технология винтового соединения/ номинальная площадь поперечного сечения 2,5 мм2,Степень защиты: IP 20 ,,Вход датчик NAMUR согласно EN 60947 , 8 В DC / 8 мА электропитание датчика, 0...5 кГц частота на входе , Обнаружение обрыва провода,Выход реле 1 нормально разомкнутый контакт, 250 В AC / 30 В DC @ 2 A, безопасная область, 32 В AC @ 0,5 A/ 32 В DC @ 1 A, зона 2,Выход аварийной сигнализации - реле 1 нормально разомкнутый контакт, 250 В AC / 30 В DC @ 2 A, безопасная область, 32 В AC @ 0,5 A/ 32 В DC @ 1 A, зона 2,Электропитание 19...31,2 В DC,Мощность потерь прим. 1,8 Вт,Диапазон температур,окружающей среды -20 °C...+60 °C,,,Надежная развязка EN 61010, 3-канальная гальваническая развязка до 2,6 кВ AC/DC всех цепей относительно друг друга,Рабочее напряжение 300 В AC/DC при категории перенапряжения II и классе загрязнения 2,Сертификаты cULus, ATEX IECEX, FM ,,ATEX-маркировка II 3 G ExnA nC IIC T4 ,ATEX-данные U0 = 10, 6 В DC, I0 = 12 мА DC, P0 = 32 Вт,,Тип ACT20X-HDI-SDO-RNO-S
- Текст описания, сокращенный Усилитель-разъединитель для датчиков Namur для применения во взрывоопасных зонах Ex, ,1-канальный усилитель-разъединитель с монтажной шириной 22,5 мм с внешним электропитанием,,для развязки и передачи сигналов датчика Namur из зоны Ex 0, 1, 2 в безопасную зону. ,На выходе предоставляется беспотенциальный релейный контакт с функцией нормально разомкнутого контакта и контакт аварийной сигнализации для ,сообщений о состоянии/ ошибке.,Предусмотрена возможность конфигурирования модуля при помощи стандартного программного обеспечения FDT/DTM.
- Температура хранения -20 °C...85 °C
- Температура хранения, макс. 85 °C
- Температура хранения, мин. -20 °C
- Технические данные EPLAN, WSCAD
- Тип Реле, 1 нормально замкнутый контакт (беспотенциальный)
- Тип изделия Преобразователь сигналов
- Тип устройства B
- Ток I0 12 mA DC
- Уровень мощности ≤ 62.5 ВA / 32 Вт (защищенная зона),≤ 16 ВA / 32 Вт (Зона 2)
- Функциональность Выход = вход, прямой или инверсный (возможность конфигурирования)
- Функция аварийной сигнализации Обрыв цепи на входе, Короткое замыкание на входе, Отсутствует напряжение питания, Ошибка устройства
- Частота на входе, макс. < 20 Гц
- Номер для заказа 8965340000
- Ширина 22,5 мм
Последние
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
TOP
Общие данные | |
Average Probability of Failure on Demand (PFDavg) | 2.04 x 10-4 (Tproof = 1 year), 4.08 x 10-4 (Tproof = 2 years), 1.02 x 10-4 (Tproof = 5 years) |
Demand mode | High |
Demand rate | 1 000 s |
Demand response time | < 10 ms (relay output) |
Description of the "safe state" | de-energized (relay output) |
Diagnostic test interval | 10 s |
Mean Time To Repair (MTTR) | 8 h |
MTBF | 207 Years |
NAMUR-питание | 8 V DC / 8 mA |
Relay lifetime | 100000 times |
Safe Failure Fraction (SFF) | 90 % |
SIL PAPER | SIL certificate |
SIL согласно IEC 61508 | 2 |
Total failure rate for dangerous detected failures (λDD) | 130 FIT |
Total failure rate for dangerous undetected failures (λDU) | 46 FIT |
Total failure rate for safe detected failures (λSD) | 0 FIT |
Total failure rate for safe undetected failures (λSU) | 289 FIT |
Tproof | 4 Years |
Брошюра / каталог | CAT 4.1 ELECTR 16/17 EN |
Вероятность отказа в час PFH | 4.66 x 10-8 h-1 |
Вид защиты | IP20 |
Вид соединения | Винтовое соединение, Съемный клеммный блок |
Влажность | 0...95 % (без появления конденсата) |
Входное сопротивление | 1 кОм |
Высокий пороговый уровень | > 2.1 мA |
Высота | 117,2 мм |
Выходной сигнал при обрыве провода | < 0.1 мA, > 6.5 мA |
Глубина | 113,6 мм |
Глубина (дюймов) | 4,472 inch |
Датчик | NAMUR-Чувствительность в соответствии с EN60947, переключение с или без RS, RP |
Диапазон зажима, макс. | 2,5 mm² |
Диапазон зажима, мин. | 0,5 mm² |
Диапазон размеров зажимаемых проводников, измерительное соединение, | 2,5 mm² |
Длительность импульса | < 0,1 мс |
Исполнение | EX-преобразователь сигналов, Вход Ex: датчик/коммутатор NAMUR, Безоп. выход: реле, контакт НР, 1-канальн. |
Категория безопасности | SIL 2 |
Коммутационная способность AC | 500 ВА/60 Вт (безопасная область), 16 ВА/60 Вт (зона 2) |
Конфигурация | с программным обеспечением FDT/DTM |
Масса нетто | 177 g |
Момент затяжки, макс. | 0,6 Nm |
Момент затяжки, мин. | 0,4 Nm |
Мощность P0 | 32 mW |
Напряжение U0 | 10.6 В DC |
Напряжение питания | 19,2…31,2 В DC |
Напряжение развязки | 2 кВ, вход / выход / питание |
Непрерывный ток | ≤ 0,5 A AC / 0,3 A DC (безопасная зона), ≤ 0,5 A AC / 1 A DC (зона 2) |
Низкий уровень триггера | < 1.2 мA |
Номинальное рабочее напряжение | ≤ 125 В AC / 110 В DC (взрывозащенная область),≤ 32 В AC / 32 В DC (Зона 2) |
Норма упаковки (VPE) | 1 Шт. |
Нормы по ЭМС | DIN EN 61326, NE 21 |
Обозначение | II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I |
Одобрение / сертификат / документ о соответствии | SIL certificate Certification DNV GL Declaration of Conformity |
Отказоустойчивость оборудования (HFT) | 0 |
Питание датчика | 8 V DC / 8 mA |
Пользовательская документация | Instruction sheet Manual MAN SAFETY ACT20X-(2)HDI-(2)SDO-RNx |
Поперечное сечение подключаемого провода AWG, макс. | AWG 14 |
Поперечное сечение подключаемого провода AWG, мин. | AWG 30 |
Потребляемая мощность | ≤ 1,3 Вт |
Программное обеспечение | WI-Manager, DTM-Library for online installation V.1.2.0 |
Рабочая температура | -20 °C...60 °C |
Рабочая температура, макс. | 60 °C |
Рабочая температура, мин. | -20 °C |
Расчетное напряжение | 300 В |
Сведения об изделии | Для этого устройства компания Weidmüller предоставляет увеличенный гарантийный период (36 месяцев). |
Сертификат ATEX | 09ATEX0168X.pdf |
Сертификат IECEx | IECEx certification |
Сертификат UL | E337701.pdf |
Сертификат № (ATEX) | KEMA09ATEX0168X |
Сертификат № (IECEX) | IECEXKEM09.0072X |
Сопротивление | RP = 750 Ω / RS = 15kΩ |
Текст описания, длинный | Усилитель-разъединитель для датчиков Namur для применения во взрывоопасных зонах Ex, ,1-канальный усилитель-разъединитель с монтажной шириной 22,5 мм с внешним электропитанием,,для развязки и передачи сигналов датчика Namur из зоны Ex 0, 1, 2 в безопасную зону. ,На выходе предоставляется беспотенциальный релейный контакт с функцией нормально разомкнутого контакта и контакт аварийной сигнализации для ,сообщений о состоянии/ ошибке.,Предусмотрена возможность конфигурирования модуля при помощи стандартного программного обеспечения FDT/DTM.Корпус для установки в ряд на монтажную рейку TS35,Размеры: Д/Ш/В 119,2/ 22,5/ 113,6,Технология винтового соединения/ номинальная площадь поперечного сечения 2,5 мм2,Степень защиты: IP 20 ,,Вход датчик NAMUR согласно EN 60947 , 8 В DC / 8 мА электропитание датчика, 0...5 кГц частота на входе , Обнаружение обрыва провода,Выход реле 1 нормально разомкнутый контакт, 250 В AC / 30 В DC @ 2 A, безопасная область, 32 В AC @ 0,5 A/ 32 В DC @ 1 A, зона 2,Выход аварийной сигнализации - реле 1 нормально разомкнутый контакт, 250 В AC / 30 В DC @ 2 A, безопасная область, 32 В AC @ 0,5 A/ 32 В DC @ 1 A, зона 2,Электропитание 19...31,2 В DC,Мощность потерь прим. 1,8 Вт,Диапазон температур,окружающей среды -20 °C...+60 °C,,,Надежная развязка EN 61010, 3-канальная гальваническая развязка до 2,6 кВ AC/DC всех цепей относительно друг друга,Рабочее напряжение 300 В AC/DC при категории перенапряжения II и классе загрязнения 2,Сертификаты cULus, ATEX IECEX, FM ,,ATEX-маркировка II 3 G ExnA nC IIC T4 ,ATEX-данные U0 = 10, 6 В DC, I0 = 12 мА DC, P0 = 32 Вт,,Тип ACT20X-HDI-SDO-RNO-S |
Текст описания, сокращенный | Усилитель-разъединитель для датчиков Namur для применения во взрывоопасных зонах Ex, ,1-канальный усилитель-разъединитель с монтажной шириной 22,5 мм с внешним электропитанием,,для развязки и передачи сигналов датчика Namur из зоны Ex 0, 1, 2 в безопасную зону. ,На выходе предоставляется беспотенциальный релейный контакт с функцией нормально разомкнутого контакта и контакт аварийной сигнализации для ,сообщений о состоянии/ ошибке.,Предусмотрена возможность конфигурирования модуля при помощи стандартного программного обеспечения FDT/DTM. |
Температура хранения | -20 °C...85 °C |
Температура хранения, макс. | 85 °C |
Температура хранения, мин. | -20 °C |
Технические данные | EPLAN, WSCAD |
Тип | Реле, 1 нормально замкнутый контакт (беспотенциальный) |
Тип изделия | Преобразователь сигналов |
Тип устройства | B |
Ток I0 | 12 mA DC |
Уровень мощности | ≤ 62.5 ВA / 32 Вт (защищенная зона),≤ 16 ВA / 32 Вт (Зона 2) |
Функциональность | Выход = вход, прямой или инверсный (возможность конфигурирования) |
Функция аварийной сигнализации | Обрыв цепи на входе, Короткое замыкание на входе, Отсутствует напряжение питания, Ошибка устройства |
Частота на входе, макс. | < 20 Гц |
Номер для заказа | 8965340000 |
Размеры и массы | |
Ширина | 22,5 мм |
Рекомендуемые
TOP
TOP
TOP
TOP
TOP
TOP
TOP